This work focus on observation of the insulating system and analysis of the insulation resistance measurement results in 110kV, 20 and 63 MVA oil-immersed power transformers are presented. The observation was undertaken from the start-up and it includes graphical and numerical values obtained by measurements, the analysis of the state of insulation provides possibilities to undertake remedial action in due time with the aim to extend the transformer life.
The power transformer represents one of the most important functional components of a power facility, In addition, taking into account the development of electric machines the transformer happens to be among the very first to be developed, Under operating conditions its life extends to about 30 years, Observation of its functional behavior during its life offers important data that may be used as a basis for improvement of its design, technology, for intermediate action under operating conditions all with the aim to extend its life, Generally speaking the transformer represents a complex unit consisting of the following fundamental systems: conductive system - magnetic system- insulating system -supporting system (structure) -protective system.
Each of these systems represents an important and inseparable part with respect to the transformer as a whole. Besides, analysis of its component parts proves to be an interesting experience. Each of the complex system mentioned above includes several subsystems that deserve special consideration and attention. ln this paper, the insulation system is presented. This system plays key role in the functioning of the unit and due to its sensitivity and complexity it requires very close consideration as to its design and engineering and technological aspects. Observation of the insulating system by means of selected methods (insulation testing by means of a mega ohmmeter) over a number of years gives a general idea of the insulation state, roughly speaking, the insulating system can be divided into:
Bushings (porcelain) -oil part - cellulose (paper, wood) part - coating-resins (sheet metal, winding.) - Geometry (gaps).
The following methods have been used for observation of the insulation ageing - Current-voltage measurements (a method)-inductor measurements (mega ohmmeter)-ultrasonic measurements-winding loss angle measurements-chemical analysis, chromatography - capacitance and inductivity measurements. Enclosed in the paper is the figure showing the insulating system observed by a single method over a given period of years. We have selected the inductor measurement method of observation for presentation of the insulating system. This method is known for its adaptability to the operating conditions, fast procurement of results, simple instruments and mobility. This method provides a general idea of the insulation system state. The diagrams and tables show the state of insulating system for five (5), 110/35/10kV, 20 and 63 MVA transformers. These results have been reduced to 20C temperature and they refer to transformers in operation exposed to all conditions that normally happen in a network (over voltages, short-circuits, fluctuation of load, etc.) including all lightning phenomena. Figure 1 illustrates in the best way the behavior of insulation resistance on a transformer in which the insulation level decreased after the commissioning in the factory.
As shown in Figure 2 the permanent decline of insulation, there is no improvement after energizing the transformer either as shown on Figure 3, for MV and LV- Ground. Experience related to other transformers show that an improvement would normally occur after setting the transformer into operation. This is probably due to the elimination of the residual humidity from the system.
Figure 3 shows continuous decline of insulation resistance which can be explained by insufficient loading and oil heating (drying) after the start-up which did not allow any significant improvement to occur. A transformer which managed to maintain its insulating properties on a permanent level over a 17-year period of operation because it functioned under nearly nominal conditions as shown in Figure 4
Figure 5 shows a transformer in which a deviation from its characteristics of R15 and R60 for HV and MD-Ground took place. These deviations could be most probably attributed to measurement errors. After one year, the transformer was energized immediately after the installation and over a period of. four subsequent years continuous improvement of the insulation resistance took place, After these, there. came a period of expected decline of insulation properties as a result of the normal ageing process It must be emphasized that measurement method provides approximate results that night serve for the insulation state estimation although it has been strongly influenced by wither conditions, by the fact , , that different measuring instruments were used, by the precision of readings, etc. The observation carried out provides interesting data which proved that such observations are useful and important. In order to obtain a general state estimation it is required to carry out the observations during the entire life of the transformer, This approach enables procurement of data which can be used as a guide for necessary steps that are needed to slow down the ageing process and extension of the transformer useful life.
Table 1 illustrate the Transformer: o1 "Amman, 110/33/11KV 20 MVA, the insulation resistance has been reduced to 20c0 temperature.
Table 2 shows the Transformer: "Jo2" Amman, 110/33/11KV 63 MVA, insulation resistance has been reduced to 20c0 temperature
The observation and analysis of insulation under operating conditions is of utmost importance. The observation results allow to carry out insulation state estimation and to predict future tendencies in its behavior. They also provide basis for defining necessary steps and remedial action aimed at extension of transformer useful life. Among other things, the results reflect the quality of insulating materials used; The following advantage is the possibility to plan auxiliary transformer requirements in cases when accelerated decline of insulation becomes evident. The data concerning the state of insulation may become important background data for new transformer developments.
[1] | “IEEE Std C57.12.90-1999”, IEEE Standard Test Code for Liquid Immersed Distribution Power and Regulating Transformer. | ||
In article | |||
[2] | “Measurement of relative permittivity dielectric dissipation factor and, d.c. resistivity of insulating liquids”, IEC 60247. | ||
In article | |||
[3] | Wang, M., Vandermaar, A.J., and Srivastava, K.D., “Review of condition assessment of power transformers in service,” IEEE Electr. Insulat. Mag.,, Vol. 18, pp. 12-25, 2002. | ||
In article | View Article | ||
[4] | Singh, J., Sood, Y.R., and Verma, P., “Experimental investigation using accelerated aging factors on dielectric properties of transformer insulating oil,” Electr. Power Compon. Syst., Vol. 39, pp.1045-1059, 2011 | ||
In article | View Article | ||
[5] | Shroff, D.H., and Stannett, A.W., “A review of paper ageing in power transformers,” Proc. IEE, Vol. 132, pp. 312-319, 1985. | ||
In article | View Article | ||
[6] | T. X. Xue, B. Xie, and Y. Lu: Study on The Insulation Life Models Of Power Transformer “, IEEE, 2008. | ||
In article | View Article | ||
[7] | W Young, Transformer life management- condition monitoring, Proceedings of the 1998 IEE Colloquium on transformers life, IEE Colloquium(Digest)IEE Stevange, Engl, p2/1-2/4 | ||
In article | View Article | ||
[8] | Romero, A.A., Mombello, E.E. and Rattá, G., An overview on power transformer management: Individual assets and fleets, Transmission and Distribution Latin America Conference and Exposition (T&D-LA), Sixth IEEE/PES, pp. 1-7, 2012. | ||
In article | PubMed | ||
[9] | Susa, D. and Nordman, H., A simple model for calculating transformer hot spot temperature, IEEE Transactions on Power Delivery, 24(3), pp. 1257-1265, 2009. | ||
In article | |||
[10] | CIGRE, Moisture equilibrium and moisture migration within transformer insulation systems, Vol. A2.30, Ed, 2008. | ||
In article | View Article | ||
[11] | Fofana, I., Borsi, H. and Gockenbach, E., Fundamental investigations on some transformer liquids under various outdoor conditions, IEEE Transactions on Dielectrics and Electrical Insulation, 8(6), pp. 1040-1047, 2001. | ||
In article | View Article | ||
[12] | Gelegenis, J.J., Estimation of hourly temperature data from their monthly average values: case study of Greece, Renewable Energy, 18(1), pp. 49-60, 1999. | ||
In article | View Article | ||
[13] | Gomez-Luna, E., Duarte, C., Aponte, G., Guerra, J.P. and Goossen, K.W., Experiences with non-intrusive monitoring of distribution transformers based on the on-line frequency response, Ingeniería e Investigación, 35(1) , pp. 55-59, 2015. | ||
In article | View Article | ||
[14] | Crine J.P.; “On the interpretation of some electrical aging and relaxatio phenomena in solid dielectrics”, IEEE Transactions on Dielectrics and Electrical Insulation, 2005, Vol. 12, No.6, pp.1089-1107. | ||
In article | View Article | ||
[15] | Muthanna K.T., Sarkar A., Das K., Waldner K.; “Transformer insulation life assessment”, IEEE Transactions on Power Delivery, 2006, Vol. 21, No. 1, pp. 150-156. | ||
In article | View Article | ||
Published with license by Science and Education Publishing, Copyright © 2018 khalaf Y. Alzyoud
This work is licensed under a Creative Commons Attribution 4.0 International License. To view a copy of this license, visit https://creativecommons.org/licenses/by/4.0/
[1] | “IEEE Std C57.12.90-1999”, IEEE Standard Test Code for Liquid Immersed Distribution Power and Regulating Transformer. | ||
In article | |||
[2] | “Measurement of relative permittivity dielectric dissipation factor and, d.c. resistivity of insulating liquids”, IEC 60247. | ||
In article | |||
[3] | Wang, M., Vandermaar, A.J., and Srivastava, K.D., “Review of condition assessment of power transformers in service,” IEEE Electr. Insulat. Mag.,, Vol. 18, pp. 12-25, 2002. | ||
In article | View Article | ||
[4] | Singh, J., Sood, Y.R., and Verma, P., “Experimental investigation using accelerated aging factors on dielectric properties of transformer insulating oil,” Electr. Power Compon. Syst., Vol. 39, pp.1045-1059, 2011 | ||
In article | View Article | ||
[5] | Shroff, D.H., and Stannett, A.W., “A review of paper ageing in power transformers,” Proc. IEE, Vol. 132, pp. 312-319, 1985. | ||
In article | View Article | ||
[6] | T. X. Xue, B. Xie, and Y. Lu: Study on The Insulation Life Models Of Power Transformer “, IEEE, 2008. | ||
In article | View Article | ||
[7] | W Young, Transformer life management- condition monitoring, Proceedings of the 1998 IEE Colloquium on transformers life, IEE Colloquium(Digest)IEE Stevange, Engl, p2/1-2/4 | ||
In article | View Article | ||
[8] | Romero, A.A., Mombello, E.E. and Rattá, G., An overview on power transformer management: Individual assets and fleets, Transmission and Distribution Latin America Conference and Exposition (T&D-LA), Sixth IEEE/PES, pp. 1-7, 2012. | ||
In article | PubMed | ||
[9] | Susa, D. and Nordman, H., A simple model for calculating transformer hot spot temperature, IEEE Transactions on Power Delivery, 24(3), pp. 1257-1265, 2009. | ||
In article | |||
[10] | CIGRE, Moisture equilibrium and moisture migration within transformer insulation systems, Vol. A2.30, Ed, 2008. | ||
In article | View Article | ||
[11] | Fofana, I., Borsi, H. and Gockenbach, E., Fundamental investigations on some transformer liquids under various outdoor conditions, IEEE Transactions on Dielectrics and Electrical Insulation, 8(6), pp. 1040-1047, 2001. | ||
In article | View Article | ||
[12] | Gelegenis, J.J., Estimation of hourly temperature data from their monthly average values: case study of Greece, Renewable Energy, 18(1), pp. 49-60, 1999. | ||
In article | View Article | ||
[13] | Gomez-Luna, E., Duarte, C., Aponte, G., Guerra, J.P. and Goossen, K.W., Experiences with non-intrusive monitoring of distribution transformers based on the on-line frequency response, Ingeniería e Investigación, 35(1) , pp. 55-59, 2015. | ||
In article | View Article | ||
[14] | Crine J.P.; “On the interpretation of some electrical aging and relaxatio phenomena in solid dielectrics”, IEEE Transactions on Dielectrics and Electrical Insulation, 2005, Vol. 12, No.6, pp.1089-1107. | ||
In article | View Article | ||
[15] | Muthanna K.T., Sarkar A., Das K., Waldner K.; “Transformer insulation life assessment”, IEEE Transactions on Power Delivery, 2006, Vol. 21, No. 1, pp. 150-156. | ||
In article | View Article | ||